無功補償在低壓電網中重要性和必要性
眾所周知無功補償就是借助于相應的無功補償裝置提(ti)供必要的(de)無功(gong)(gong)(gong)功(gong)(gong)(gong)率,以提(ti)高功(gong)(gong)(gong)率因數,降低能耗,改善(shan)電(dian)網(wang)質量。各級電(dian)網(wang)和輸配(pei)電(dian)設(she)備都(dou)要消(xiao)耗一定數量的(de)無功(gong)(gong)(gong)功(gong)(gong)(gong)率,而低壓配(pei)電(dian)網(wang)所占比(bi)重(zhong)非常大。采(cai)用無功(gong)(gong)(gong)補償技術,提(ti)高低壓電(dian)網(wang)和用電(dian)設(she)備的(de)功(gong)(gong)(gong)率因數,已成為節電(dian)工作的(de)一項重(zhong)要方(fang)法。
一、影響功率(lv)因(yin)數(shu)的(de)主(zhu)要因(yin)素
異步(bu)電(dian)動機和電(dian)力(li)變壓(ya)器(qi)是(shi)(shi)耗用無(wu)功(gong)(gong)功(gong)(gong)率(lv)的(de)(de)(de)主要(yao)設備。異步(bu)電(dian)動機所耗用的(de)(de)(de)無(wu)功(gong)(gong)功(gong)(gong)率(lv)是(shi)(shi)由其空(kong)載(zai)(zai)時(shi)的(de)(de)(de)無(wu)功(gong)(gong)功(gong)(gong)率(lv)和一定負載(zai)(zai)下無(wu)功(gong)(gong)功(gong)(gong)率(lv)增加(jia)值兩部分所組成。變壓(ya)器(qi)消耗無(wu)功(gong)(gong)的(de)(de)(de)主要(yao)成份是(shi)(shi)它的(de)(de)(de)空(kong)載(zai)(zai)無(wu)功(gong)(gong)功(gong)(gong)率(lv)供(gong)電(dian)電(dian)壓(ya)超出規定范圍也(ye)會(hui)影響功(gong)(gong)率(lv)因數(shu)。所以要(yao)尋求一些(xie)(xie)行之有效的(de)(de)(de)、能(neng)夠使低(di)壓(ya)電(dian)力(li)網功(gong)(gong)率(lv)因數(shu)提高的(de)(de)(de)一些(xie)(xie)實用方法,使低(di)壓(ya)網能(neng)夠實現無(wu)功(gong)(gong)的(de)(de)(de)就(jiu)地平衡,達到(dao)降(jiang)損節能(neng)的(de)(de)(de)效果。
二(er)、低壓配(pei)電網無功補(bu)償方法(fa)
提高功(gong)率因數的主要方(fang)法是(shi)采(cai)用低壓無功(gong)補償(chang)(chang)技術,我(wo)們通常采(cai)用的方(fang)法主要有(you)三種:隨機補償(chang)(chang)、隨器(qi)補償(chang)(chang)、跟蹤補償(chang)(chang)。
(1) 隨機(ji)(ji)補(bu)償:將(jiang)低壓電容器(qi)組與電動(dong)機(ji)(ji)并接,通過(guo)控(kong)制、保護裝置(zhi)與電機(ji)(ji),同時(shi)投(tou)切的隨機(ji)(ji)補(bu)償適用于補(bu)償電動(dong)機(ji)(ji)的無功消耗,以補(bu)勵磁無功為主。而且配置(zhi)方便靈(ling)活,不需頻(pin)繁調整補(bu)償容量。投(tou)資少、安裝簡便。
(2) 隨(sui)器(qi)補(bu)償:將低壓電容器(qi)通(tong)過(guo)低壓保險接在配(pei)(pei)電變(bian)(bian)壓器(qi)二次側,以補(bu)償配(pei)(pei)電變(bian)(bian)壓器(qi)空載無(wu)(wu)功(gong)(gong)的補(bu)償方(fang)式。它能有效(xiao)地補(bu)償配(pei)(pei)變(bian)(bian)空載無(wu)(wu)功(gong)(gong)。限制(zhi)農網無(wu)(wu)功(gong)(gong)基荷,使該部分(fen)無(wu)(wu)功(gong)(gong)就地平衡(heng),從(cong)而提(ti)高(gao)配(pei)(pei)變(bian)(bian)利用率,降(jiang)低無(wu)(wu)功(gong)(gong)網損,是目前補(bu)償無(wu)(wu)功(gong)(gong)最有效(xiao)的手段(duan)之一。
(3)跟(gen)蹤(zong)補償(chang):是指以無(wu)功補償(chang)投切(qie)裝(zhuang)置(zhi)作(zuo)為控制保護(hu)裝(zhuang)置(zhi),將低(di)壓電(dian)容器組補償(chang)在(zai)大用(yong)(yong)戶(hu)0.4KV母(mu)線上的補償(chang)方式。適用(yong)(yong)于100KVA以上的專用(yong)(yong)配變用(yong)(yong)戶(hu),可以替(ti)代隨機、隨器兩種(zhong)補償(chang)方式,補償(chang)效果好。
三、無(wu)功功率補(bu)償容量的(de)選擇方法(fa)
無功(gong)補(bu)償(chang)容量(liang)(liang)以提高(gao)功(gong)率因數為主要目的(de)時(shi),補(bu)償(chang)容量(liang)(liang)的(de)選擇分(fen)兩(liang)大類討(tao)論,即單負(fu)荷就(jiu)地補(bu)償(chang)容量(liang)(liang)的(de)選擇(主要指(zhi)(zhi)電(dian)動機)和(he)多負(fu)荷補(bu)償(chang)容量(liang)(liang)的(de)選擇( 指(zhi)(zhi)集(ji)中和(he)局部分(fen)組(zu)補(bu)償(chang))。
3.1 單負荷就(jiu)地補償容量的(de)選擇
(1)美國資料推薦:Qc=(1/3)Pe(額定容量的(de)1/3)
(2)經驗(yan)系數(shu)法(fa):由于電機極數(shu)不(bu)同,按極數(shu)大小確定經驗(yan)系數(shu)選擇容(rong)量(liang)比較接近實際需要(yao)的電容(rong)器,采用這種方法(fa)一(yi)般在(zai)70%負荷時,補后功率(lv)因數(shu)可在(zai)0.95~0.97之間。
3.2 多負荷補(bu)償(chang)容(rong)量(liang)的選擇
多負荷補償容(rong)量的(de)選擇(ze)是根(gen)據(ju)補償前后的(de)功率因數來確(que)定。
安徽(hui)得潤(run)電氣歡迎(ying)新老(lao)顧客隨時致電400-0551-777咨詢無功補償的相關問題,并樂(le)于為您服務。
掃一掃二維碼了解(jie)更多詳(xiang)情(qing):
得潤電氣(qi)訂閱號(hao)
得(de)潤電氣(qi)頭(tou)條號
更多詳情請咨詢安徽得潤電氣技術有限公司
“推薦閱讀”
- 在設計施耐德Blokset低壓柜時需要注意哪些細節?
- 從安倍遇害談開關柜配電室安全
- 2022年ABB授權柜MNS2.0低壓開關柜有哪些改變
- 收藏了!UniSafe中壓授權柜基礎知識詳解
- UniSafe中壓授權柜|助力污水處理廠建設高質量發展
- 年末將至|得潤電氣一批批開關柜發往項目現場
- 給您不一樣的ABB高壓中置式開關柜的新體驗
- 10kV開關柜KYN28A-12高壓柜的成本核算找誰
- 從35KV及以下的高低壓開關柜 授權柜 誰可以直接供貨
- Schneider低壓授權柜Blokset產品一問一答
【責任編輯】:安徽得潤(run)電(dian)氣得潤電氣版權所有://bandei.cn轉載請注明出處